6×4 m raised freestanding deck – plans, timber list and sizes

This 6×4 m raised freestanding deck (24.0 m²) is carried by joists 45×120 at 596 mm c/c on beams 45×220 and posts 95×95, 12 footings in total. The sizes are calculated for 2.5 kN/m² imposed load and snow zone 2.0 – the cheapest combination of standard timber that passes bending, shear and deflection.

Frame drawing: 6×4 m raised freestanding deck
Frame drawing · 6×4 m raised freestanding deck · Download drawing (PNG)

Quick facts

Area
24.0 m²
Joists
45×120 c/c 596
Beams
45×220
Posts
12 × 95×95
Footings
12
Boards
23
Total timber
89 m

Member sizes

MemberSizeUtilisationGoverning
Joistsspan 1.98 m · c/c 596 mm · g 0.14 kN/m, q 1.49 kN/m 45×120 c/c 596 99% deflection
Beams3 rows · span 1.87 m between posts · g 0.51 kN/m, q 4.94 kN/m 45×220 85% shear
Postslength 0.78 m · N 10.2 kN (G+Q) · unbraced, Lef = 2L 95×95 22% buckling

Joist size by imposed load

Imposed load (kN/m²)Size
2.0 45×120 c/c 596
2.5 45×120 c/c 596
3.5 45×145 c/c 596
4.0 45×145 c/c 596

Timber list

QtySizeLengthTreatment
11 45×120 4.2 m Pressure treated NTR/AB
4 45×120 3.3 m Pressure treated NTR/AB
4 45×220 4.2 m Pressure treated NTR/AB
1 45×220 2.1 m Pressure treated NTR/AB
2 95×95 4.2 m Pressure treated NTR/AB
1 95×95 2.4 m Pressure treated NTR/AB

Good to know

FAQ

What size joists do I need for a 6×4 m raised freestanding deck?

45×120 at 596 mm c/c is enough for 2.5 kN/m² imposed load. That uses 99% of the capacity under Eurocode 5.

How big do the beams need to be?

The beams are 45×220. Always join beams over a post.

How much timber does it take?

The frame takes 23 boards in standard lengths, 89 m of timber in total. The cut list is optimised to keep offcuts small.

How many footings do I need?

12 footings. The most heavily loaded one carries 10.2 kN, which on firm friction soil means a footing of roughly Ø300–400 mm.

Similar plans

All plans → · Markdown version